E CLIPS
Each
of the installations are to be installed in series. The protected side goes towards the
equipment to be protected. To
maintain proper continuity, exit on the terminal screw that is directly
opposite, A to A and B to B. These
units may be affixed to wall or
other mounting surface by screw
holes at either end of TVSS housing.
The GROUND WIRE MUST BE CONNECTED to the nearest unified ground to
avoid possible ground loops. The
best source for unified ground is at the line side of the 120HWCP20CB. This will also provide an alternative
path flow around your panel to ground.
A special DDual 2WDTB/G 5V is available for PC board to Case Ground
application. The purpose of the
DDual 2WDTB/G5V is to eliminate surge from the ground side up through the
case into the PC board due to near by lightning ground strikes. Initiating
Circuits: (Class A) requires two FA24V, (Class B) requires
one FA24V. Install the FA24 for
Zones with the protected side facing the PC Board. Tie ground to the line side of
120HWCP20CB (unprotected). Notification
Appliances: (30 volts +3 amps) requires FA30VBHB, (34.4
volts +3 amps) requires FA60VBNC .
Install the FA30 or FA60 for the Notification Appliance with the
protected side facing the PC Board. Tie ground on line side of 120HWCP20CB.
Power
Supply: Install the
120HWCP20CB with the load side (protected ) facing the power supply.
Install all ground wires from low voltage surge suppressors zones,
notification appliances, and PC board ground to line side of 120HWCP20CB (unprotected). PC
Board Ground: If ground wire is tied to from screw on PC
board to Case, a DDual2WDTB/G5V
is available. Install the
DDual2WDTB/G5V with the protected side facing the PC board, and ground wire
to line side of 120HWCP20CB (unprotected). Communication:
Install the DLTTOS 30V for the data line and the DLTTOS 200V (two required)
for the tip and ring on the RJ31X application.Tie the ground back to the
line side of 120HWCP20CB (unprotected).
If a surge
suppressor does blow, the unit has a life time warranty, and will be
replaced at no charge from the manufacture. As it stands,
there seems to be no possible way to eliminate the ground loops. What is required is that you low voltage
surge suppressors, and the AC surge suppressors be able to with-stand 6000
volts at 3000 amps impulse and keep ticking. Your let through voltage must be no more then 238 volts AC
and 34.4 volts DC. If there are
any questions, please call me at 888-471-1038 Ask for John
Pecore Stormin
Protection Products Inc. 10749 63rd
Way N. Pinellas
Park, FL. 33782
OH OH UG UG UG UG UG UG = UNDER
GROUND OH = OVERHEAD MILL RIVER LUMBER = 2– COND. HORN
& INITIATION CIRCUITS = 4-CONDUCTOR
DATA WIRE = SUB-FIRE PANEL KILN 3 KILN 2 KILN 1 STORAGE PLANNER CUT SHOP MAIN FIRE PANEL OFFICE SHOP MILL
Stormin Protection
Products, http://www.storminprotection.com
10749
63rd Way N.
Pinellas
Park, FL. 33782
888-471-1038
Toll Free
727-548-5418
Phone
727-548-0867
fax
120HWCP20CB 1 unit
Retail $263.00 Total $263.00
120HWCP15 4 units Retail
$111.00 $444.00
FA 30 VB 7 units Retail $69.95 $489.65
FA 30BH 16 units Retail $69.95 $1119.20
Total value $2315.85
Retail
I am making
recommendations regarding grounding, based on ground loops.
I do recommend if
at all possible to provide a shield wire to one grounding source f
or all
applications, but in this case it is not possible.
I would like to
speak to you more on this subject before this is finished.
I hope you have a
clear picture what needs to be bought, and installed.
This is only a Sample of the last
recommendation I did.
Click here for Index Click her for Page 21 Click here for Page 23