Protector / Hardwire / PTS 120 H / 2nd Edition
Specifications - Operating: Maximum Operating Voltage: 120 Volts AC Typical Leakage Current: <5µ
amps Operation Temperature: -
40 to +85°C Connectors: Hardwired Installation Configuration: Parallel Specifications - Electronic: Maximum Surge Current (8x20µs): 100,000 Amps Total Maximum Surge Voltage (1.2x50µs): 10,000 Volts Capacitance: <2,000
pf Clamping Voltage: 130
Volts RMS Clamping Response Time: <5
nanoseconds Current: Non-Load
Bearing Voltage: Voltage
Sensitive Design: Thermally
Fused Hybrid Operation Indicators: Light
Emitting Diode (LED) Power Dissipation (8x20µs): 13,000,000
Volts Amps Energy Dissipation: 950
Joules UL 1449: 1449
Second Edition UL Recognized Component: File
E121637 USL and CNL Approved: United
States / Canada Dimension: Depth
2.25" Width
2.844" Length 5.694”
(including tabs) Weight: Approximately
1lbs. Pass Voltage Tested to ANSI/IEEE B3 Impulse: UL’s Best 330 V Peak
Rating E-Clips surge
suppressors have a Lifetime Product
Warranty. Please see warranty
statement for complete product warranty information. Click here for Index Click here for Main
Panel Page PE Info Down load PTS120H
Down Load
Lines Protected: L-N,
N-G, L-G